Multi-Apartment Air Conditioning

Single Apartment Systems – Small – Multiple Indoor Units

(Quick View Reference: 2a to 2d)

A simple air cooled split air conditioning system’s operation involves:-

  • Heat is transferred between the outside ambient air and refrigerant within the outdoor condensing unit.
  • Refrigerant is delivered from the condensing units to indoor fan coil units within the apartment.
  • Heat is transferred between the refrigerant within the fan coil unit and the air within the conditioned space.
  • The system arrangement includes; a single outside condensing unit, consisting of compressor/s, condenser coil, discharge fan/s and associated electronics serving single or multiple indoor units.
  • Insulated refrigerant piping connected between the condensing unit and each fan coil unit.
  • Associated system control panels and temperature sensors.

small ac condenser1 to multi wall hung

Capacity: Various E.g. 5 kWr to 12 kWr

Condensers Locations:

  • Located on each balcony in accordance with manufacturers requirements.
  • Grouped on well ventilated platforms
  • Within well ventilated plant rooms, typically with fan assisted heat rejection.

Considerations:

Typically with domestic sized units the heat rejection fan have virtually no ability to overcome any external resistance from enclosures and the like.

When grouping condensers, it is critical heat discharged via the fan is able to be removed from the air intake otherwise short circuiting occurs and causes condenser failure.

When groups of condensers are staked above each other (floor by floor) in still conditions a heat plume can be created with the effect that higher floor levels air intake temperature is elevated (thus causing condenser failure).

Locating condensers in car parks is not recommended due to short circulating issues. A small residential condenser can typically have 1900 l/s of discharge air at c. 10 oC above ambient. Thus, for example on a 34 oC day, warm air at 44 oC will occur.

Provision of an isolator per unit is required

Condensate will occur. Provide means to remove

Mount units off floor to limit corrosion.

Provide bi-gold or similar treatment to condenser coils when located in salt areas or in high pollution areas.

Pipework Limitations

The distance between condenser and indoor units horizontally and vertically is limited (and manufacturer particular).

 5.2 kWr Capacity (2 heads)

 2heads
 2heads tech data.png

5.4 kWr Capacity (3 heads)

 3 heads
 3 heads tech data

7.4 kWr Capacity (4 heads)

 4 heads
 7 kw 4 head tech data

8.0 kWr Capacity (4 heads)

 4 heads 8 kwr.png
 8 kW 4 heads tech data.png

10 kWr Capacity (5 heads)

 5 heads
 5 heads tech data.png

12 kWr Capacity (6 heads)

 6 heads.png
 6 head tech data.png

Note: Each pipe bend reduces the available length of pipework

Pipework should be run in individual apartments space (for that apartments AC condenser) or in common areas.

 Zoning

With 1 to multi systems (1 condenser and multiple indoor units) 1 head per room is typically provided. Small capacity units (c. 5 kWr) have up to 2 indoor units and larger capacity units (c. 12 kWr) can have up to 6 indoor units.

No. Ports Condenser Model Capacity (kWr) ERR Condenser Noise

 (SPL dBA)

Link
2 MXZ-2C52VA Min: 3.9

Max: 11

3.44 45 – 49  

Link

3 MXZ-3C54VA Min: 2.9

Max: 6.8

4.3 45 – 47

Link

4 MXZ-4C71VA Min: 3.7

Max: 8.8

4.02 45 – 48

 Link

5 MXZ-5C100VA Min: 3.9

Max: 11

3.44 46 – 51  

Link

6 MXZ-6C120VA Min: 3.5

Max: 13.5

3.21 51 – 55  

Link

Controls

Controls are normally proprietary & supplied by unit manufacturer.

Often the controller is not fixed and the controller is aimed at each indoor unit to gain operation (infra red).

Heating & Cooling

Cooling Only

Cooling only systems are suitable where heating of a conditioned space is not required. This is generally not the case.

Reverse Cycle

Reverse cycle systems have the ability to cool and heat, however only simultaneous cooling or simultaneous heating can be accommodated by all fan coil units connected to a single condensing unit. Therefore all rooms within an apartment served by a reverse cycle system can only be provided with either cooling or heating at any one time.

Heat Recovery: Heat recovery system types are not available.

Future Proofing

AC units should be considered for internet connection allowing for:

  • Faults to be emailed
  • Manufacturer connection to review faults
  • Remote app based start/stopping etc.

Ownership & Billing: Refer 1 to 1 Ownership & Billing